Sales02@aotewell.com

Tel: +86-133-6088-1849

WhatsApp / Wechat / Mobile

Schneider Drives ATV212HD18N4  Current Product

Part Nr: ATV212HD18N4 Schneider variable speed drive, Altivar 212, 18.5kW, 25hp, 480V

Brand: Schneider  Type: Drives
State: Check Stock 

Buy Schneider Schneider ATV212HD18N4 at DCS-Centers.com, Best price and Big Stock.

variable speed drive, Altivar 212, 18.5kW, 25hp, 480V, 3 phases, with EMC, IP21

ATV212HD18N4

Main
Device short name ATV212
Product destination Asynchronous motors
Phase 3 phase
Motor power kW 18.5 kW
Maximum Horse Power Rating 25 hp
Supply voltage limits 323…528 V
Supply frequency 50…60 Hz – 5…5 %
Line current 27.8 A 480 V
34.8 A 380 V
Range of Product Altivar 212
Product or Component Type Variable speed drive
Product Specific Application Pumps and fans in HVAC
Communication Port Protocol APOGEE FLN
BACnet
LonWorks
Modbus
METASYS N2
[Us] rated supply voltage 380…480 V – 15…10 %
EMC filter Class C2 EMC filter integrated
IP degree of protection IP21
Complementary
Apparent power 28.2 kVA 380 V
Continuous output current 37 A 380 V
37 A 460 V
Maximum transient current 40.7 A 60 s
Speed drive output frequency 0.5…200 Hz
Speed range 1…10
Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
Local signalling for DC bus energized 1 LED (red)
Output voltage <= power supply voltage
Isolation Electrical between power and control
Type of cable Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR
Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC
With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC
Electrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.004 in² (2.5 mm²) / AWG 14
L1/R, L2/S, L3/T terminal 0.04 in² (25 mm²) / AWG 3
Tightening torque 5.3 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
39.8 lbf.in (4.5 N.m), 40 lb.in L1/R, L2/S, L3/T)
Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection
Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection
Sampling duration 2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
3.5 ms +/- 0.5 ms VIA analog
22 ms +/- 0.5 ms VIB analog
Response time FM 2 ms +/- 0.5 ms analog
FLA, FLC 7 ms +/- 0.5 ms discrete
FLB, FLC 7 ms +/- 0.5 ms discrete
RY, RC 7 ms +/- 0.5 ms discrete
Accuracy +/- 0.6 % VIA) for a temperature variation 60 °C
+/- 0.6 % VIB) for a temperature variation 60 °C
+/- 1 % FM) for a temperature variation 60 °C
Linearity error VIA +/- 0.15 % of maximum value input
VIB +/- 0.15 % of maximum value input
FM +/- 0.2 % output
Analogue output type FM switch-configurable voltage 0…10 V DC 7620 Ohm 10 bits
FM switch-configurable current 0…20 mA 970 Ohm 10 bits
Discrete output type Configurable relay logic FLA, FLC) NO – 100000 cycles
Configurable relay logic FLB, FLC) NC – 100000 cycles
Configurable relay logic RY, RC) NO – 100000 cycles
Minimum switching current 3 mA 24 V DC configurable relay logic
Maximum switching current 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)
2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Discrete input type F programmable 24 V DC level 1 PLC 4700 Ohm
R programmable 24 V DC level 1 PLC 4700 Ohm
RES programmable 24 V DC level 1 PLC 4700 Ohm
Discrete input logic Positive logic (source) F, R, RES), <= 5 V, >= 11 V
Negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance >= 1 mOhm 500 V DC for 1 minute
Frequency resolution Display unit 0.1 Hz
Analog input 0.024/50 Hz
communication service Time out setting from 0.1 to 100 s
Read device identification (43)
Monitoring inhibitable
Read holding registers (03) 2 words maximum
Write multiple registers (16) 2 words maximum
Write single register (06)
Option card Communication card LonWorks
Power dissipation in W 603 W
Air flow 56533.8 Gal/hr(US) (214 m3/h)
Functionality Mid
Specific application HVAC
Variable speed drive application selection Building – HVAC compressor for scroll
Building – HVAC fan
Building – HVAC pump
Motor power range AC-3 15…25 kW 380…440 V 3 phase
15…25 kW 480…500 V 3 phase
Motor starter type Variable speed drive
Discrete output number 2
Analogue input number 2
Analogue input type VIA switch-configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits
VIB configurable voltage 0…10 V DC 24 V max 30000 Ohm 10 bits
VIB configurable PTC probe 0…6 probes 1500 Ohm
VIA switch-configurable current 0…20 mA 250 Ohm 10 bits
Analogue output number 1
Physical interface 2-wire RS 485
Connector Type 1 open style
1 RJ45
Transmission Rate 9600 bps or 19200 bps
Transmission frame RTU
Number of addresses 1…247
Data format 8 bits, 1 stop, odd even or no configurable parity
Type of polarization No impedance
Asynchronous motor control profile Voltage/frequency ratio, 5 points
Voltage/frequency ratio – Energy Saving, quadratic U/f
Voltage/frequency ratio, 2 points
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Flux vector control without sensor, standard
Torque accuracy +/- 15 %
Transient overtorque 120 % of nominal motor torque +/- 10 % 60 s
Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 3200 s
Automatic based on the load
Motor slip compensation Not available in voltage/frequency ratio motor control
Automatic whatever the load
Adjustable
Switching frequency 6…16 kHz adjustable
8…16 kHz with derating factor
Nominal switching frequency 8 kHz
Braking to standstill By DC injection
Network Frequency 47.5…63 Hz
Prospective line Isc 22 kA
Protection type Overheating protection drive
Thermal power stage drive
Short-circuit between motor phases drive
Input phase breaks drive
Overcurrent between output phases and earth drive
Overvoltages on the DC bus drive
Break on the control circuit drive
Against exceeding limit speed drive
Line supply overvoltage and undervoltage drive
Line supply undervoltage drive
Against input phase loss drive
Thermal protection motor
Motor phase break motor
With PTC probes motor
Width 9.6 in (245 mm)
Height 13.0 in (330 mm)
Depth 7.5 in (190 mm)
Net Weight 25.68 lb(US) (11.65 kg)
Environment
Pollution degree 2 IEC 61800-5-1
IP degree of protection IP20 on upper part without blanking plate on cover IEC 61800-5-1
IP20 on upper part without blanking plate on cover IEC 60529
IP21 IEC 61800-5-1
IP21 IEC 60529
IP41 on upper part IEC 61800-5-1
IP41 on upper part IEC 60529
Vibration resistance 1.5 mm 3…13 Hz)IEC 60068-2-6
1 gn 13…200 Hz)EN/IEC 60068-2-8
Shock resistance 15 gn 11 ms IEC 60068-2-27
Environmental characteristic Classes 3C1 IEC 60721-3-3
Classes 3S2 IEC 60721-3-3
Noise level 54 dB 86/188/EEC
Operating altitude 3280.84…9842.52 ft (1000…3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
<= 3280.84 ft (1000 m) without derating
Relative humidity 5…95 % without condensation IEC 60068-2-3
5…95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation 14…104 °F (-10…40 °C) without derating)
104…122 °F (40…50 °C) with derating factor)
Operating position Vertical +/- 10 degree
Product Certifications CSA
UL
C-tick
NOM 117
marking CE
Standards IEC 61800-3 environments 1 category C2
IEC 61800-3 category C2
IEC 61800-3
IEC 61800-3 environments 1 category C1
IEC 61800-5-1
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 1 category C2
EN 55011 class A group 1
IEC 61800-3 environments 1 category C3
IEC 61800-3 environments 1 category C3
IEC 61800-3
IEC 61800-3 category C3
EN 61800-3 category C3
IEC 61800-3 category C2
IEC 61800-5-1
UL Type 1
IEC 61800-3 environments 2 category C3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-3 environments 2 category C1
Assembly style With heat sink
Electromagnetic compatibility Electrostatic discharge immunity test level 3 IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 IEC 61000-4-4
1.2/50 µs – 8/20 µs surge immunity test level 3 IEC 61000-4-5
Conducted radio-frequency immunity test level 3 IEC 61000-4-6
Voltage dips and interruptions immunity test IEC 61000-4-11
Regulation loop Adjustable PI regulator
Ambient Air Temperature for Storage -13…158 °F (-25…70 °C)
Ordering and shipping details
Category US1CP4D22157
Discount Schedule CP4D
GTIN 3606480322532
Returnability Yes
Country of origin US

parts photo album​

a:1:{i:0;s:14:”Payment by T/T”;}

ATV212HD18N4 Schneider variable speed drive, Altivar 212, 18.5kW, 25hp, 480V

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor
Hot Sell

Click edit button to change this text. Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Customer feedback
9/10

People who viewed this item also viewed

Made in French

Click edit button to change this text. Lorem ipsum dolor sit amet consectetur adipiscing elit dolor

ATV212HD18N4 Schneider variable speed drive, Altivar 212, 18.5kW, 25hp, 480V

Welcome to send your RFQ

Please provide your detailed information below, we will contact you within 24 hours and arrange for a business manager to provide you with a quotation