Main |
Range of Product |
Altivar 32 |
Product or Component Type |
Variable speed drive |
Product destination |
Synchronous motors |
Asynchronous motors |
Product Specific Application |
Complex machines |
Function Available |
– |
Assembly style |
With heat sink |
Component name |
ATV32 |
EMC filter |
Class C2 EMC filter integrated |
Phase |
3 phase |
[Us] rated supply voltage |
380…500 V – 15…10 % |
Supply voltage limits |
323…550 V |
Supply frequency |
50…60 Hz – 5…5 % |
Network Frequency |
47.5…63 Hz |
Motor power kW |
5.5 kW 380…480 V |
Maximum Horse Power Rating |
7.5 hp 380…480 V |
Complementary |
Line current |
14.5 A 500 V 3 phase 5.5 kW / 7.5 hp |
20.7 A 380 V 3 phase 5.5 kW / 7.5 hp |
Apparent power |
17.9 kVA 500 V 3 phase 5.5 kW / 7.5 hp |
Prospective line Isc |
22 kA 3 phase |
Nominal output current |
14.3 A 4 kHz 500 V 5.5 kW / 7.5 hp |
Maximum transient current |
21.5 A 60 s 5.5 kW / 7.5 hp |
Output frequency |
0.0005…0.599 kHz |
Nominal switching frequency |
4 kHz |
Switching frequency |
2…16 kHz adjustable |
Speed range |
1…100 asynchronous motor in open-loop mode |
Speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn |
Torque accuracy |
+/- 15 % |
Transient overtorque |
170…200 % |
Braking torque |
<= 170 % with braking resistor |
Asynchronous motor control profile |
Flux vector control without sensor, standard |
Flux vector control without sensor – Energy Saving, NoLoad law |
Voltage/frequency ratio, 5 points |
Voltage/frequency ratio – Energy Saving, quadratic U/f |
Voltage/frequency ratio, 2 points |
Synchronous motor control profile |
Vector control without sensor |
Regulation loop |
Adjustable PID regulator |
Motor slip compensation |
Automatic whatever the load |
Adjustable 0…300 % |
Not available in voltage/frequency ratio (2 or 5 points) |
Local signalling |
1 LED red drive voltage |
1 LED green CANopen run |
1 LED red CANopen error |
1 LED red drive fault |
Output voltage |
<= power supply voltage |
Noise level |
43 dB 86/188/EEC |
Insulation |
Electrical between power and control |
Electrical connection |
Screw terminal 0.5…1.5 mm², AWG 18…AWG 14 control) |
Removable screw terminals 2.5…16 mm², AWG 12…AWG 6 motor/braking resistor) |
Screw terminal 4…16 mm², AWG 10…AWG 6 power supply) |
Tightening torque |
4.4 lbf.in (0.5 N.m), 4.4 lb/ft control) |
10.6 lbf.in (1.2 N.m), 10.6 lb/ft motor/braking resistor) |
10.6 lbf.in (1.2 N.m), 10.6 lb/ft power supply) |
Supply |
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection |
Analogue input number |
3 |
Analogue input type |
AI1 voltage 0…10 V DC 30000 Ohm 10 bits |
AI2 bipolar differential voltage +/- 10 V DC 30000 Ohm 10 bits |
AI3 current 0…20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration) 250 Ohm 10 bits |
Sampling duration |
2 ms AI1, AI2, AI3) – analog |
2 ms AO1) – analog |
Response time |
LI1…LI6 8 ms +/- 0.7 ms logic |
R1A, R1B, R1C 2 ms relay |
R2A, R2C 2 ms relay |
Accuracy |
+/- 0.2 % AI1, AI2, AI3) for a temperature of -10…60 °C |
+/- 0.5 % AI1, AI2, AI3) for a temperature of 25 °C |
+/- 1 % AO1) for a temperature of 25 °C |
+/- 2 % AO1) for a temperature of -10…60 °C |
Linearity error |
+/- 0.2…0.5 % of maximum value AI1, AI2, AI3) |
+/- 0.3 % AO1) |
Analogue output number |
1 |
Analogue output type |
AO1 software-configurable current 0…20 mA 800 Ohm 10 bits |
AO1 software-configurable voltage 0…10 V 470 Ohm 10 bits |
Discrete output number |
3 |
Discrete output type |
Configurable relay logic R1A, R1B, R1C) NO/NC – 100000 cycles |
Configurable relay logic R2A, R2B) NO – 100000 cycles |
Logic LO) |
Minimum switching current |
5 mA 24 V DC configurable relay logic |
Maximum switching current |
R1 3 A 250 V AC resistive, cos phi = 1 |
R1 4 A 30 V DC resistive, cos phi = 1 |
R1, R2 2 A 250 V AC inductive, cos phi = 0.4 |
R1, R2 2 A 30 V DC inductive, cos phi = 0.4 |
R2 5 A 250 V AC resistive, cos phi = 1 |
R2 5 A 30 V DC resistive, cos phi = 1 |
Discrete input number |
7 |
Discrete input type |
Programmable (sink/source) LI1…LI4)24…30 V DC level 1 PLC |
Programmable as pulse input 20 kpps LI5)24…30 V DC level 1 PLC |
Switch-configurable PTC probe LI6)24…30 V DC |
Safe torque off STO)24…30 V DC – 1500 Ohm |
Discrete input logic |
Negative logic (sink) LI1…LI6), > 19 V, < 13 V |
Positive logic (source) LI1…LI6), < 5 V, > 11 V |
Acceleration and deceleration ramps |
Linear |
Ramp switching |
Deceleration ramp automatic stop DC injection |
CUS |
S |
U |
Deceleration ramp adaptation |
Braking to standstill |
By DC injection |
Protection type |
Input phase breaks drive |
Overcurrent between output phases and earth drive |
Overheating protection drive |
Short-circuit between motor phases drive |
Thermal protection drive |
Communication Port Protocol |
CANopen |
Modbus |
Connector type |
1 RJ45 on front face)Modbus/CANopen |
Physical interface |
2-wire RS 485 Modbus |
Transmission frame |
RTU Modbus |
Type of polarization |
No impedance Modbus |
Number of addresses |
1…127 CANopen |
1…247 Modbus |
Method of access |
Slave CANopen |
Electromagnetic compatibility |
1.2/50 µs – 8/20 µs surge immunity test, level 3 IEC 61000-4-5 |
Conducted radio-frequency immunity test, level 3 IEC 61000-4-6 |
Electrical fast transient/burst immunity test, level 4 IEC 61000-4-4 |
Electrostatic discharge immunity test, level 3 IEC 61000-4-2 |
Radiated radio-frequency electromagnetic field immunity test, level 3 IEC 61000-4-3 |
Voltage dips and interruptions immunity test IEC 61000-4-11 |
Width |
5.9 in (150 mm) |
Height |
12.1 in (308 mm) |
Depth |
9.1 in (232 mm) |
Net Weight |
16.5 lb(US) (7.5 kg) |
Option card |
Communication card CANopen daisy chain |
Communication card CANopen open style |
Communication card DeviceNet |
Communication card EtherNet/IP |
Communication card Profibus DP V1 |
Functionality |
Mid |
Specific application |
Other applications |
Environment |
Standards |
EN/IEC 61800-5-1 |
EN 61800-3 environments 2 category C2 |
EN/IEC 61800-3 |
EN 55011 class A group 1 |
EN 61800-3 environments 1 category C2 |
Product Certifications |
CSA |
UL |
GOST |
C-tick |
NOM 117 |
Marking |
CE |
Pollution degree |
2 EN/IEC 61800-5-1 |
IP degree of protection |
IP20 EN/IEC 61800-5-1 |
Vibration resistance |
1 gn 13…200 Hz) EN/IEC 60068-2-6 |
1.5 mm peak to peak 3…13 Hz) EN/IEC 60068-2-6 |
Shock resistance |
15 gn 11 msEN/IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation IEC 60068-2-3 |
5…95 % without dripping water IEC 60068-2-3 |
Ambient air temperature for operation |
14…122 °F (-10…50 °C) without derating |
122…140 °F (50…60 °C) with derating factor |
Ambient Air Temperature for Storage |
-13…158 °F (-25…70 °C) |
Operating altitude |
<= 3280.84 ft (1000 m) without derating |
3280.84…9842.52 ft (1000…3000 m) with current derating 1 % per 100 m |
Operating position |
Vertical +/- 10 degree |