Main |
Range of product |
Altivar 61 |
Product or component type |
Variable speed drive |
Product specific application |
Pumping and ventilation machine |
Component name |
ATV61 |
Motor power kW |
55 kW, 3 phases at 380…480 V |
Motor power hp |
75 hp, 3 phases at 380…480 V |
power supply voltage |
380…480 V – 15…10 % |
supply number of phases |
3 phases |
Line current |
101 A for 480 V 3 phases 55 kW / 75 hp |
120 A for 380 V 3 phases 55 kW / 75 hp |
EMC filter |
Level 3 EMC filter |
Variant |
Without remote graphic terminal |
Assembly style |
With heat sink |
Apparent power |
79 kVA at 380 V 3 phases 55 kW / 75 hp |
maximum prospective line Isc |
22 kA for 3 phases |
Maximum transient current |
139.2 A for 60 s, 3 phases |
Nominal switching frequency |
12 kHz |
Switching frequency |
1…16 kHz adjustable |
12…16 kHz with derating factor |
asynchronous motor control |
Voltage/frequency ratio, 5 points |
Voltage/frequency ratio, 2 points |
Voltage/frequency ratio – Energy Saving, quadratic U/f |
Flux vector control without sensor, standard |
Synchronous motor control profile |
Vector control without sensor, standard |
Communication port protocol |
Modbus |
CANopen |
Type of polarization |
No impedance for Modbus |
Option card |
Communication card for APOGEE FLN |
Communication card for BACnet |
Communication card for CC-Link |
Controller inside programmable card |
Communication card for DeviceNet |
Communication card for EtherNet/IP |
Communication card for Fipio |
I/O extension card |
Communication card for Interbus-S |
Communication card for LonWorks |
Communication card for METASYS N2 |
Communication card for Modbus Plus |
Communication card for Modbus TCP |
Communication card for Modbus/Uni-Telway |
Multi-pump card |
Communication card for Profibus DP |
Communication card for Profibus DP V1 |
Complementary |
Product destination |
Asynchronous motors |
Synchronous motors |
power supply voltage limits |
323…528 V |
power supply frequency |
50…60 Hz – 5…5 % |
power supply frequency limits |
47.5…63 Hz |
Continuous output current |
116 A at 12 kHz, 380 V – 3 phases |
96 A at 12 kHz, 460 V – 3 phases |
Output frequency |
0.1…500 Hz |
Speed range |
1…100 in open-loop mode, without speed feedback |
Speed accuracy |
+/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback |
Torque accuracy |
+/- 15 % in open-loop mode, without speed feedback |
Transient overtorque |
130 % of nominal motor torque +/- 10 % for 60 s |
Braking torque |
<= 125 % with braking resistor |
30 % without braking resistor |
Regulation loop |
Frequency PI regulator |
Motor slip compensation |
Adjustable |
Automatic whatever the load |
Can be suppressed |
Not available in voltage/frequency ratio (2 or 5 points) |
diagnostic |
1 LED (red) for drive voltage |
Output voltage |
<= power supply voltage |
electrical isolation |
Between power and control terminals |
type of cable for mounting in an enclosure |
With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC |
With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |
Electrical connection |
Terminal 2.5 mm² / AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
Terminal 150 mm² / 300 kcmil (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Tightening torque |
0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC, +/- 5 %, <10 mA with overload and short-circuit protection |
Internal supply: 24 V DC (21…27 V), <200 mA with overload and short-circuit protection |
External supply: 24 V DC (19…30 V) |
Analogue input number |
2 |
Analogue input type |
AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign |
AI2 software-configurable current: 0…20 mA, impedance: 242 Ohm, resolution 11 bits |
AI2 software-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits |
sampling time |
2 ms +/- 0.5 ms (AI1-/Al1+) – analog input |
2 ms +/- 0.5 ms (Al2) – analog input |
2 ms +/- 0.5 ms (AO1) – analog output |
2 ms +/- 0.5 ms (LI1…LI5) – discrete input |
2 ms +/- 0.5 ms (LI6)if configured as logic input – discrete input |
absolute accuracy precision |
+/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C |
+/- 0.6 % (AI2) for a temperature variation 60 °C |
+/- 1 % (AO1) for a temperature variation 60 °C |
Linearity error |
+/- 0.15 % of maximum value (AI1-/Al1+) |
+/- 0.15 % of maximum value (AI2) |
+/- 0.2 % (AO1) |
Analogue output number |
1 |
Analogue output type |
AO1 software-configurable current, analogue output range 0…20 mA, impedance: 500 Ohm, resolution 10 bits |
AO1 software-configurable voltage, analogue output range 0…10 V DC, impedance: 470 Ohm, resolution 10 bits |
AO1 software-configurable logic output 10 V, 20 mA |
Discrete output number |
2 |
Discrete output type |
Configurable relay logic: (R1A, R1B, R1C) NO/NC – 100000 cycles |
Configurable relay logic: (R2A, R2B) NO – 100000 cycles |
maximum response time |
<= 100 ms in STO (Safe Torque Off) |
R1A, R1B, R1C <= 7 ms, tolerance +/- 0.5 ms |
R2A, R2B <= 7 ms, tolerance +/- 0.5 ms |
Minimum switching current |
3 mA at 24 V DC for configurable relay logic |
Maximum switching current |
R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4 and L/R = 7 ms |
R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4 and L/R = 7 ms |
R1, R2: 5 A at 250 V AC resistive load, cos phi = 1 and L/R = 0 ms |
R1, R2: 5 A at 30 V DC resistive load, cos phi = 1 and L/R = 0 ms |
Discrete input number |
7 |
Discrete input type |
Programmable (LI1…LI5)24 V DC (<= 30 V), with level 1 PLC – 3500 Ohm |
Switch-configurable (LI6)24 V DC (<= 30 V), with level 1 PLC – 3500 Ohm |
Switch-configurable PTC probe (LI6)0…6 probes – 1500 Ohm |
Safety input (PWR)24 V DC (<= 30 V) – 1500 Ohm |
Discrete input logic |
Negative logic (sink) (LI1…LI5), > 16 V (state 0), < 10 V (state 1) |
Positive logic (source) (LI1…LI5), < 5 V (state 0), > 11 V (state 1) |
Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1) |
Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1) |
Acceleration and deceleration ramps |
S, U or customized |
Linear adjustable separately from 0.01 to 9000 s |
Automatic adaptation of ramp if braking capacity exceeded, by using resistor |
Braking to standstill |
By DC injection |
Protection type |
Against exceeding limit speed: drive |
Against input phase loss: drive |
Break on the control circuit: drive |
Input phase breaks: drive |
Line supply overvoltage: drive |
Line supply undervoltage: drive |
Overcurrent between output phases and earth: drive |
Overheating protection: drive |
Overvoltages on the DC bus: drive |
Power removal: drive |
Short-circuit between motor phases: drive |
Thermal protection: drive |
Motor phase break: motor |
Power removal: motor |
Thermal protection: motor |
Insulation resistance |
> 1 mOhm 500 V DC for 1 minute to earth |
Frequency resolution |
Analog input: 0.024/50 Hz |
Display unit: 0.1 Hz |
Connector type |
1 RJ45 (on front face) for Modbus |
1 RJ45 (on terminal) for Modbus |
Male SUB-D 9 on RJ45 for CANopen |
Physical interface |
2-wire RS 485 for Modbus |
Transmission frame |
RTU for Modbus |
Transmission rate |
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal |
9600 bps, 19200 bps for Modbus on front face |
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen |
Data format |
8 bits, 1 stop, even parity for Modbus on front face |
8 bits, odd even or no configurable parity for Modbus on terminal |
Number of addresses |
1…127 for CANopen |
1…247 for Modbus |
Method of access |
Slave CANopen |
Marking |
CE |
Operating position |
Vertical +/- 10 degree |
Net weight |
44 kg |
Width |
320 mm |
Height |
630 mm |
Depth |
290 mm |
Environment |
Noise level |
63.7 dB conforming to 86/188/EEC |
Dielectric strength |
3535 V DC between earth and power terminals |
5092 V DC between control and power terminals |
Electromagnetic compatibility |
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 |
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
Standards |
IEC 60721-3-3 class 3S2 |
IEC 61800-5-1 |
IEC 60721-3-3 class 3C1 |
IEC 61800-3 environments 1 category C3 |
EN 55011 class A group 2 |
IEC 61800-3 |
UL Type 1 |
IEC 61800-3 environments 2 category C3 |
Product certifications |
CSA |
NOM 117 |
UL |
GOST |
DNV |
C-Tick |
Pollution degree |
3 conforming to IEC 61800-5-1 |
3 conforming to UL 840 |
degree of proctection |
IP20 on upper part without blanking plate on cover conforming to IEC 60529 |
IP20 on upper part without blanking plate on cover conforming to IEC 61800-5-1 |
IP21 conforming to IEC 60529 |
IP21 conforming to IEC 61800-5-1 |
IP41 on upper part conforming to IEC 60529 |
IP41 on upper part conforming to IEC 61800-5-1 |
IP54 on lower part conforming to IEC 60529 |
IP54 on lower part conforming to IEC 61800-5-1 |
Vibration resistance |
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
Shock resistance |
15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation conforming to IEC 60068-2-3 |
5…95 % without dripping water conforming to IEC 60068-2-3 |
Ambient air temperature for operation |
-10…50 °C (without derating) |
50…60 °C (with derating factor) |
Ambient air temperature for storage |
-25…70 °C |
Operating altitude |
<= 1000 m without derating |
1000…3000 m with current derating 1 % per 100 m |