Main |
Range of product |
Altivar 71 |
Product or component type |
Variable speed drive |
Product specific application |
Complex, high-power machines |
Component name |
ATV71 |
Motor power kW |
22 kW, 3 phases at 380…480 V |
Motor power hp |
30 hp, 3 phases at 380…480 V |
Maximum motor cable length |
100 m shielded cable |
200 m unshielded cable |
power supply voltage |
380…480 V – 15…10 % |
Network number of phases |
3 phases |
Line current |
42 A for 480 V 3 phases 22 kW / 30 hp |
50 A for 380 V 3 phases 22 kW / 30 hp |
EMC filter |
Integrated |
Assembly style |
With heat sink |
Variant |
Without remote graphic terminal |
Apparent power |
32.9 kVA at 380 V 3 phases 22 kW / 30 hp |
Prospective line Isc |
22 kA for 3 phases |
Nominal output current |
40 A at 4 kHz 460 V 3 phases 22 kW / 30 hp |
48 A at 4 kHz 380 V 3 phases 22 kW / 30 hp |
Maximum transient current |
72 A for 60 s 3 phases 22 kW / 30 hp |
79.2 A for 2 s 3 phases 22 kW / 30 hp |
Output frequency |
0.1…599 Hz |
Nominal switching frequency |
4 kHz |
Switching frequency |
1…16 kHz adjustable |
4…16 kHz with derating factor |
Asynchronous motor control profile |
Voltage/frequency ratio (2 or 5 points) |
Flux vector control (FVC) with sensor (current vector) |
Sensorless flux vector control (SFVC) (voltage or current vector) |
ENA (Energy adaptation) system for unbalanced loads |
Type of polarization |
No impedance for Modbus |
Complementary |
Product destination |
Synchronous motors |
Asynchronous motors |
power supply voltage limits |
323…528 V |
power supply frequency |
50…60 Hz – 5…5 % |
power supply frequency limits |
47.5…63 Hz |
Speed range |
1…100 for asynchronous motor in open-loop mode, without speed feedback |
1…1000 for asynchronous motor in closed-loop mode with encoder feedback |
1…50 for synchronous motor in open-loop mode, without speed feedback |
Speed accuracy |
+/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn |
+/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn |
Torque accuracy |
+/- 15 % in open-loop mode, without speed feedback |
+/- 5 % in closed-loop mode with encoder feedback |
Transient overtorque |
170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes |
220 % of nominal motor torque +/- 10 % for 2 s |
Braking torque |
<= 150 % with braking or hoist resistor |
30 % without braking resistor |
Synchronous motor control profile |
Vector control without speed feedback |
Regulation loop |
Adjustable PI regulator |
Motor slip compensation |
Suppressable |
Not available in voltage/frequency ratio (2 or 5 points) |
Automatic whatever the load |
Adjustable |
diagnostic |
1 LED (red) for drive voltage |
Output voltage |
<= power supply voltage |
Insulation |
Electrical between power and control |
type of cable for mounting in an enclosure |
With a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC |
With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC |
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR |
Electrical connection |
Terminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
Terminal, clamping capacity: 50 mm², AWG 1/0 (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Tightening torque |
0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1…LI6, PWR) |
12 N.m, 102.2 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB) |
Supply |
Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Internal supply: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection |
Analogue input number |
2 |
Analogue input type |
AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign |
AI2 software-configurable current: 0…20 mA, impedance: 242 Ohm, resolution 11 bits |
AI2 software-configurable voltage: 0…10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits |
input sampling time |
2 ms +/- 0.5 ms (AI1-/Al1+) – analog input(s) |
2 ms +/- 0.5 ms (Al2) – analog input(s) |
2 ms +/- 0.5 ms (LI1…LI5) – discrete input(s) |
2 ms +/- 0.5 ms (LI6)if configured as logic input – discrete input(s) |
Response time |
<= 100 ms in STO (Safe Torque Off) |
AO1 2 ms, tolerance +/- 0.5 ms for analog output(s) |
R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
absolute accuracy precision |
+/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C |
+/- 0.6 % (AI2) for a temperature variation 60 °C |
+/- 1 % (AO1) for a temperature variation 60 °C |
Linearity error |
+/- 0.15 % of maximum value (AI1-/Al1+, AI2) |
+/- 0.2 % (AO1) |
Analogue output number |
1 |
Analogue output type |
AO1 software-configurable logic output 10 V 20 mA |
AO1 software-configurable current 0…20 mA, impedance: 500 Ohm, resolution 10 bits |
AO1 software-configurable voltage 0…10 V DC, impedance: 470 Ohm, resolution 10 bits |
Discrete output number |
2 |
Discrete output type |
Configurable relay logic: (R1A, R1B, R1C) NO/NC – 100000 cycles |
Configurable relay logic: (R2A, R2B) NO – 100000 cycles |
Minimum switching current |
3 mA at 24 V DC for configurable relay logic |
Maximum switching current |
R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4 |
R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4 |
R1, R2: 5 A at 250 V AC resistive load, cos phi = 1 |
R1, R2: 5 A at 30 V DC resistive load, cos phi = 1 |
Discrete input number |
7 |
Discrete input type |
LI1…LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm |
LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm |
LI6: switch-configurable PTC probe 0…6, impedance: 1500 Ohm |
PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d |
Discrete input logic |
Negative logic (sink) (LI1…LI5), > 16 V (state 0), < 10 V (state 1) |
Positive logic (source) (LI1…LI5), < 5 V (state 0), > 11 V (state 1) |
Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1) |
Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1) |
Acceleration and deceleration ramps |
S, U or customized |
Linear adjustable separately from 0.01 to 9000 s |
Automatic adaptation of ramp if braking capacity exceeded, by using resistor |
Braking to standstill |
By DC injection |
Protection type |
Against exceeding limit speed: drive |
Against input phase loss: drive |
Break on the control circuit: drive |
Input phase breaks: drive |
Line supply overvoltage: drive |
Line supply undervoltage: drive |
Overcurrent between output phases and earth: drive |
Overheating protection: drive |
Overvoltages on the DC bus: drive |
Short-circuit between motor phases: drive |
Thermal protection: drive |
Motor phase break: motor |
Power removal: motor |
Thermal protection: motor |
Insulation resistance |
> 1 mOhm 500 V DC for 1 minute to earth |
Frequency resolution |
Analog input: 0.024/50 Hz |
Display unit: 0.1 Hz |
Communication port protocol |
Modbus |
CANopen |
Connector type |
1 RJ45 (on front face) for Modbus |
1 RJ45 (on terminal) for Modbus |
Male SUB-D 9 on RJ45 for CANopen |
Physical interface |
2-wire RS 485 for Modbus |
Transmission frame |
RTU for Modbus |
Transmission rate |
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal |
9600 bps, 19200 bps for Modbus on front face |
20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen |
Data format |
8 bits, 1 stop, even parity for Modbus on front face |
8 bits, odd even or no configurable parity for Modbus on terminal |
Number of addresses |
1…127 for CANopen |
1…247 for Modbus |
Method of access |
Slave CANopen |
marking |
CE |
Operating position |
Vertical +/- 10 degree |
Height |
420 mm |
Depth |
236 mm |
Width |
230 mm |
Net weight |
21 kg |
Option card |
Communication card for CC-Link |
Controller inside programmable card |
Communication card for DeviceNet |
Communication card for EtherNet/IP |
Communication card for Fipio |
I/O extension card |
Communication card for Interbus-S |
Interface card for encoder |
Communication card for Modbus Plus |
Communication card for Modbus TCP |
Communication card for Modbus/Uni-Telway |
Overhead crane card |
Communication card for Profibus DP |
Communication card for Profibus DP V1 |
Environment |
Noise level |
59.9 dB conforming to 86/188/EEC |
Dielectric strength |
3535 V DC between earth and power terminals |
5092 V DC between control and power terminals |
Electromagnetic compatibility |
1.2/50 µs – 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 |
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 |
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 |
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
Standards |
UL Type 1 |
IEC 60721-3-3 class 3S2 |
IEC 60721-3-3 class 3C1 |
IEC 61800-5-1 |
IEC 61800-3 environments 2 category C3 |
IEC 61800-3 |
EN 55011 class A group 2 |
IEC 61800-3 environments 1 category C3 |
product certifications |
NOM 117 |
CSA |
C-Tick |
UL |
Pollution degree |
2 conforming to IEC 61800-5-1 |
3 conforming to UL 840 |
IP degree of protection |
IP20 on upper part without blanking plate on cover conforming to IEC 60529 |
IP20 on upper part without blanking plate on cover conforming to IEC 61800-5-1 |
IP21 conforming to IEC 60529 |
IP21 conforming to IEC 61800-5-1 |
IP41 on upper part conforming to IEC 60529 |
IP41 on upper part conforming to IEC 61800-5-1 |
IP54 on lower part conforming to IEC 60529 |
IP54 on lower part conforming to IEC 61800-5-1 |
Vibration resistance |
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6 |
Shock resistance |
15 gn for 11 ms conforming to IEC 60068-2-27 |
Relative humidity |
5…95 % without condensation conforming to IEC 60068-2-3 |
5…95 % without dripping water conforming to IEC 60068-2-3 |
Ambient air temperature for operation |
-10…50 °C (without derating) |
Ambient air temperature for storage |
-25…70 °C |
Operating altitude |
<= 1000 m without derating |
1000…3000 m with current derating 1 % per 100 m |